Radiant Panel Association
QUICK REFERENCE
to RPA Guidelines for Hydronic Radiant Floor Heating
Special Insulation Considerations
Location |
Application |
Min. R-Value |
Coverage |
| Slab on Grade | Alternate #1 | *(Ti-To) 0.125 |
Perimeter to below frost line |
| Alternate #2 | R-5 |
4' horizontal or vertical at perimeter | |
| Alternate #3 | R-5 |
under entire slab and slab edge | |
| Slab Below Grade | ** R-5 |
||
| Suspended Floor | |||
| Over Heated Space | Hard Surface | R-5 |
under entire floor with 2" air gap |
| Carpeted Surface | R-11 |
under entire floor with 2" air gap | |
| Over Unheated Space | Hard Surface | R-13 |
under entire floor with 2" air gap |
| Carpeted Surface | R-19 |
under entire floor with 2" air gap | |
| Walls with Panels | Outside Wall | R-13 |
entire wall |
| Inside Wall | optional |
||
| Ceiling Panels | Inside Ceiling | R-11 |
entire ceiling above panel |
| Outside Ceiling | R-30 |
entire ceiling above panel |
Pressure Testing Embedded Tubing -
Floor Surface Temperatures -
Fluid Temperatures -
Floor Covering - R-value not to exceed design requirement
Tube Placement -
Tube Length -
| Tube Size |
Recommended |
Maximum |
| 1/4" I.D. tubing |
100 ft. |
125 ft. |
| 3/8" I.D. tubing |
200 ft. |
250 ft. |
| 1/2" I.D. tubing |
300 ft. |
350 ft. |
| 5/8" I.D. tubing |
400 ft. |
500 ft |
| 3/4" I.D. tubing |
500 ft. |
600 ft. |
| 1" I.D. tubing |
750 ft. |
750 ft. |
| NOTE: This chart is for indoor radiant heating - not snow melting applications. | ||
Oxygen Permeation - Options: